Daikin RXYQ36PAYL [355/452] Troubleshooting

Daikin RXYQ36PAYL [355/452] Troubleshooting
Si34-803_B Troubleshooting (OP: Centralized Remote Controller)
Troubleshooting 344
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
Turn ON the power supply of
the centralized controller.
If the screen is not appearing
even tough the intelligent
Touch Controller screen is
touched or the contrast
volume is operated, replace
the intelligent Touch
Controller.
Set the Reset switch (located
inside of equipment)
SS1 been set to the Normal
side.
Replace the centralized
controller.
Correct the wiring.
Some centralized controller
gets faulty. Conduct
RUN/STOP operations on
every centralized controller,
and then replace the
centralized controller that
cannot control the indoor unit.
NO
Have power
supplies to every centralized
controller been turned
ON?
Is the display of LCD OK?
Check
the transmission
wiring of the equipment,
on which the M8 occurred, for
any broken wires.(To check for
broken wires, refer to information
in the “Procedure for
checking broken wires”
section. (Refer to
P.352)
NO
YES
Is the
Intelligent Touch
Controller used?
NO
Has the Reset
switch (located inside of
equipment) SS1 been set
to the Normal
side?
Reset the power supplies of
every centralized controller.
YES
Abnormal
Were
any changes
made to the number
of units of central
equipment? (The centralized
controller was connected once,
and then disconnected, or
additional centralized
controller was
installed.)
NO
YES
Normal
NO