Troubleshooting (OP: Centralized Remote Controller) Si34-803_B
347 Troubleshooting
4.4
MC
Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
Centralized remote controller intelligent Touch Controller
Schedule timer
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
Two or more units of centralized remote controllers and intelligent Touch Controllers are
connected, and all of them are set to master unit central setting or slave unit central setting.
Two units of schedule timers are connected.
Supposed
Causes
Address duplication of centralized controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Correct the setting of the
combination of master and
slave units, and then reset
the power supplies of every
centralized controller.
Reset the power supplies of
every centralized controller.
Replace the centralized
controller.
Centralized controller: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
NO
YES
YES
NO
Did the
malfunction
occur while in the first test
run using the intelligent
Touch Controller?
Is the
Master/Slave setting of the
centralized controller
correct?
Was the
centralized controller
connected once, and then
disconnected, or was additional
centralized controller
installed?
Is the "MC"
displayed again?
With "MC"
displayed
Without "MC"
displayed
Is the
Master/Slave setting
of the centralized
controller correct?
YES YES
If the intelligent Touch
Controller is used, correct the
setting of the combination of
master and slave units again
while in DIII-NET test run
mode, referring to the
Master/Slave setting table.
(Refer to P.349.)
NO
Turn ON the power supply of
the centralized controller with
"MC" displayed once again.
Reset the power supplies of
every centralized controller.
Be sure to
refer to the
Master/
Slave
setting
table.
(Refer to
P.348.)