Si34-803_B Troubleshooting (OP: Centralized Remote Controller)
Troubleshooting 342
4. Troubleshooting (OP: Centralized Remote
Controller)
4.1
M1
PCB Defect
Remote
Controller
Display
M1
Applicable
Models
Centralized remote controller
Schedule timer
Method of
Malfunction
Detection
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Decision
Conditions
When + polarity and - polarity are detected at the same time.
Supposed
Causes
Defect of centralized remote controller PCB
Defect of Schedule timer PCB
Troubleshooting Replace the centralized remote controller.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the M1 displayed again?
Replace the centralized
controller.
Centralized controller: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
With M1 displayed
Turn ON the power supply of
the centralized controller
with M1 displayed once again.
Without M1 displayed