Daikin RXYQ36PAYL [296/452] Outdoor unit inverter compressor motor lock

Daikin RXYQ36PAYL [296/452] Outdoor unit inverter compressor motor lock
Troubleshooting by Indication on the Remote Controller Si34-803_B
285 Troubleshooting
3.20
E5
Outdoor Unit: Inverter Compressor Motor Lock
Remote
Controller
Display
E5
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Inverter PCB takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phase-
current waveform.
Malfunction
Decision
Conditions
This malfunction will be output when the inverter compressor motor does not start up even in
forced startup mode.
Supposed
Causes
Inverter compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Faulty inverter PCB
Stop valve is left in closed.