Daikin FTKS50D2V1L [234/359] Part 6 service diagnosis

Daikin FTKS50D2V1W [234/359] Part 6 service diagnosis
SiBE12-728
Service Diagnosis 223
Part 6
Service Diagnosis
1. Caution for Diagnosis..........................................................................224
1.1 Troubleshooting with Operation Lamp .................................................224
2. Problem Symptoms and Measures .....................................................226
3. Service Check Function ......................................................................227
3.1 Check Method 1 ...................................................................................227
3.2 Check Method 2 ...................................................................................229
4. Code Indication on the Remote Controller ..........................................231
4.1 Error Codes and Description of Fault ...................................................231
5. Troubleshooting ..................................................................................232
5.1 Indoor Units ..........................................................................................232
5.2 Outdoor Units .......................................................................................233
5.3 Indoor Unit PCB Abnormality ...............................................................234
5.4 Freeze-up Protection Control or High Pressure Control.......................235
5.5 Fan Motor or Related Abnormality .......................................................237
5.6 Thermistor or Related Abnormality (Indoor Unit)..................................240
5.7 Front Panel Open / Close Fault............................................................241
5.8 Signal Transmission Error (between Indoor and Outdoor Unit) ...........242
5.9 Unspecified Voltage (between Indoor and Outdoor Units) ...................243
5.10 Freeze-up Protection Control ...............................................................244
5.11 Outdoor Unit PCB Abnormality.............................................................246
5.12 OL Activation (Compressor Overload) .................................................247
5.13 Compressor Lock .................................................................................248
5.14 DC Fan Lock ........................................................................................249
5.15 Input Over Current Detection ...............................................................250
5.16 Discharge Pipe Temperature Control...................................................252
5.17 High Pressure Control in Cooling .........................................................253
5.18 Compressor Sensor System Abnormality ............................................255
5.19 Position Sensor Abnormality ................................................................257
5.20 CT or Related Abnormality ...................................................................258
5.21 Thermistor or Related Abnormality (Outdoor Unit)...............................260
5.22 Electrical Box Temperature Rise..........................................................262
5.23 Radiation Fin Temperature Rise ..........................................................264
5.24 Output Over Current Detection.............................................................266
5.25 Insufficient Gas.....................................................................................268
5.26 Low-voltage Detection or Over-voltage Detection................................270
5.27 Signal Transmission Error (on Outdoor Unit PCB)...............................271
5.28 Anti-icing Function in Other Rooms / Unspecified Voltage
(between Indoor and Outdoor Units) ...................................................272
6. Check ..................................................................................................273
6.1 How to Check .......................................................................................273