Daikin FTKS50D2V1L [282/359] Signal transmission error on outdoor unit pcb

Daikin FTKS50D2V1W [282/359] Signal transmission error on outdoor unit pcb
SiBE12-728 Troubleshooting
Service Diagnosis 271
5.27 Signal Transmission Error (on Outdoor Unit PCB)
Remote
Controller
Display
U7
Outdoor Unit LED
Display
A
5
1
1
2
4
3
4
4
4
5
1
Method of
Malfunction
Detection
Communication error between microcomputer mounted on the main PCB and PM1.
Malfunction
Decision
Conditions
When the data sent from the PM1 can not be received successively for 9 sec.
The abnormality is determined if the above fault conditions occurs once
Fault counter is reset when the data from the PM1 can be successfully received.
Supposed
Causes
Defective outdoor unit PCB
Troubleshooting
(R7185)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
Turn off the power and turn it on
again.
Error again?
Replace the outdoor unit
PCB.
Monitor in long term.
The cause can be an
external factor other than
the malfunction.