Daikin FTKS50D2V1L [286/359] Four way valve performance check

Daikin FTXS50D2V1W [286/359] Four way valve performance check
SiBE12-728 Check
Service Diagnosis 275
6.1.4 Four Way Valve Performance Check
Check No.05
(R7156)
NO
YES
YES
NO
(Fig. 1)
Voltage at S80
DC220-240V
ON
Compressor
Time
Turn off the power and turn it on
again.
Disconnect the four way valve coil
from the connector and check the
continuity.
Start the heating-mode run.
Four way valve coil
Cooling / dry : No continuity
Heating : Continuity
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
Four way
valve coil resistance at
1500 ohms?
S80
voltage at DC 220-
240 V with compressor
on? (Fig. 1)