Daikin FTKS50D2V1L [267/359] Troubleshooting

Daikin FTXS50D2V1L [267/359] Troubleshooting
Troubleshooting SiBE12-728
256 Service Diagnosis
Troubleshooting
Connect properly.
(R7174)
NO
YES
Connect properly.
NO
YES
Replace the reactor.
NO
YES
Replace the compressor or
the compressor relay
harness
Check the operation again
and if the error appears
again, replace the outdoor
unit PCB
NO
YES
Disconnect the reactor from the outdoor
unit PCB and measure the resistance
value between reactor terminals with
tester.
Disconnect the compressor relay harness
from the outdoor unit PCB and measure
the resistance value between the terminals
of the each 3 compressor with tester.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Between all
each terminal 10or
less?
Compressor connection check
Reactor check
Compressor check
Turn off the power
Reactor connection check
Connection OK?
Connection OK?
10or less?

Содержание

Скачать