Daikin FTKS50D2V1L [253/359] Signal transmission error between indoor and outdoor unit

Daikin FTXS50D2V1W [253/359] Signal transmission error between indoor and outdoor unit
Troubleshooting SiBE12-728
242 Service Diagnosis
5.8 Signal Transmission Error (between Indoor and Outdoor
Unit)
Remote
Controller
Display
U4
Method of
Malfunction
Detection
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is
checked whether it is normal.
Malfunction
Decision
Conditions
When the data sent from the outdoor unit cannot be received normally, or when the content of
the data is abnormal.
Supposed
Causes
Faulty outdoor unit PCB / Faulty indoor unit PCB
Indoor unit-outdoor unit signal transmission error due to wiring error / due to disturbed power
supply waveform / due to breaking of wire in the connection wires between the indoor and
outdoor units (wire No. 2)
Short circuit inside the fan motor winding
Troubleshooting
Check No.10
Refer to P.279
Check the voltage of the indoor
unit-outdoor unit connection wires
between No. 1 and No. 2, and
between No 2 and No. 3.
Check No.10
Check power supply waveform.
YES
YES
Replace indoor unit control
PCB .
Locate the cause of the
disturbance of the power supply
waveform, and correct it.
NO
(R7236)
NO
YES
YES
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
Correct the indoor unit-outdoor
unit connection wires.
Diagnose the outdoor unit.
Replace the connection wires
between the indoor and
outdoor units.
Replace fan motor and outdoor
unit PCB .
Does fan rotate
smoothly?
Is LED A flashing?
Is the voltage 0 V?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit-outdoor unit
connection wires.
Check the outdoor unit's LED A.
Rotate fan by hand.