Daikin FTKS50D2V1L [247/359] Displayed the system will be reset itself but this stop will be put in the error history memory

Daikin FTKS50D2V1W [247/359] Displayed the system will be reset itself but this stop will be put in the error history memory
Troubleshooting SiBE12-728
236 Service Diagnosis
Troubleshooting
Check No.06
Refer to P.276
Note: If the outside temperature is below –10°C in the cooling mode, the system may get interrupted
with error
A5
displayed. The system will be reset itself, but this stop will be put in the error history
memory.
NO
NO
NO
Check No. 06
Indoor unit heat exchanger
thermistor check
YES
YES
(R7131)
YES
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
Does it
conform to the
thermistor characteristic
chart?
Check the intake air filter.
Check the dust accumulation on
the indoor unit heat exchanger.
Is there any short-circuit?
Is it very dirty?
Is it very dirty?
Check the air passage.