6.3 Interfaces
Manual
164 Manual, 01/2011, 6SL3097-4AC10-0BP2
6.3.4.5 X132 Digital inputs/outputs, analog input
Table 6- 12 Terminal block X132
Terminal Designation
1)
Technical specifications
1 DI/DO 8
2 DI/DO 9
3 DI/DO 10
4 DI/DO 11
As input:
input characteristics in accordance with IEC 61131-2,
Type 1
All digital inputs are floating. The reference potential is M.
Typical current consumption: 7 mA at 24 V DC
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to +5 V
DI 8, 9, 10, and 11 are "rapid inputs"
2)
Signal propagation times:
For "0" → "1": 4 μs
For "1" → "0": approx. 4 μs
As output:
Maximum load current: 100 mA
Max. leakage current: 0.5 mA
Short-circuit protected, automatic restart after short-circuit
Load types: Resistive, capacitive, inductive
Switching frequency:
For inductive load: Max. 0.5 Hz
Maximum lamp load: 2 W
5 M
6 M
Reference potential for the digital inputs/outputs and the
analog input
7 AI +
8 AI -
Differential input voltage: -10 to +10 V, maximum resolvable
range: -11 to +11 V
Common mode range: -15 V to +15 V
Resolution 13 bits
Max. connectable cross-section: 1.5 mm
2
Type: Spring-loaded terminal 1 (see Appendix A)
1) DI/DO: bidirectional digital input/output, AI: analog input; M: Electronic ground
2) The rapid inputs can be used as probe inputs or as inputs for the external zero mark
CAUTION
The common mode range may not be violated. This means that the analog differential
voltage signals can have a maximum offset voltage of +/- 15 V with respect to the reference
potential. If the range is violated, incorrect results may occur during analog/digital
conversion.
NOTICE
An open input is interpreted as "low".