Siemens 6SL3210-1SB11-0UA0 [215/318] Meaning of leds

Siemens 6SL3210-1SE23-2AA0 [215/318] Meaning of leds
Supplementary system components and encoder system integration
7.4 Sensor Module Cabinet-Mounted SMC30
Manual
Manual, 01/2011, 6SL3097-4AC10-0BP2
215
7.4.5 Meaning of LEDs
Cause and rectification of faults
The following documents contain information about the cause of faults and how they can be
rectified:
SINAMICS S120 Commissioning Manual (IH1)
SINAMICS S120/S150, List Manual (LH1)
Table 7- 18 Meaning of LEDs on the Sensor Module Cabinet SMC30
LED Color Status Description, cause Remedy
- Off Electronics power supply is missing or outside permissible
tolerance range.
Green Continuous
light
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Orange Continuous
light
DRIVE-CLiQ communication is being established.
Red Continuous
light
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Remedy and
acknowledge fault
Green/
red
Flashing
0.5 Hz
Firmware is being downloaded.
Green/
red
Flashing
2 Hz
Firmware download is complete. Wait for POWER ON. Carry out a POWER
ON
RDY
READY
Green/
orange
or
Red/
orange
Flashing
light
Component recognition via LED is activated (p0144).
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
- Off Electronics power supply is missing or outside permissible
tolerance range.
Power supply ≤ 5 V.
OUT > 5 V
Orange Continuous
light
Electronics power supply for encoder system available.
Power supply > 5 V.
Important:
Make sure that the connected encoder can be operated
with a 24 V power supply. If an encoder that is designed
for a 5 V supply is operated with a 24 V supply, this can
destroy the encoder electronics.