Daikin RQYQ16PY1 [162/194] Troubleshooting

Daikin RQYQ10PY1 [162/194] Troubleshooting
Troubleshooting by Remote Controller Si341009
153 Troubleshooting
Troubleshooting
NO
NO
YES
YES
NO
YES
YES
Connect the power supply wire
for the external control adaptor
for outdoor unit to 5V supply
line.
Replace the outdoor unit main
PCB.
Check if
the power supply
wire for the external control adaptor
for outdoor unit is connected to
5V supply line.
Replace the PCB of the external
control adaptor for outdoor unit.
Replace the outdoor unit main
PCB.
NO
YES
NO
Correct the connecting wiring
with the external control adaptor
for outdoor unit.
Diagnosis Flow 1
Check if
any disconnection or
connection error is detected in
connecting wires with external
control adaptor for
outdoor unit.
Supply the power to the outdoor
unit.
Check if power
is supplied to the
outdoor units.
Check if
the normal condition
monitor LED for the outdoor
unit PCB
blinks.
Check if
the normal condition monitor
LED for the external control
adaptor for outdoor
unit blinks.
Confirmation of error 3 Confirmation of error 4
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.