Daikin RQYQ16PY1 [83/194] Multi outdoor units connection

Daikin RQYQ24PY1 [83/194] Multi outdoor units connection
Si341009 Field Setting from Outdoor Unit
Test Operation 74
f Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Cool / Heat Select Remote Controller
Install the external control adaptor for outdoor unit on either the outdoor-outdoor, indoor-
outdoor transmission line.
Mount the COOL/HEAT selector to the unified master outdoor unit.
Set the DS1-1 on the PCB of unified master outdoor unit to OUT.
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as
the unified master, and set the other outdoor units as unified slave units.
When multiple external control adaptors for outdoor unit are used and cool / heat is selected
for each external control adaptor for outdoor unit, use “setting mode 2” and set DS1 and DS2
on the external control adaptors for outdoor unit and the unified cool / heat address
on the
outdoor unit main PCB to the same address No. (For details, refer to the following page.).
Multi outdoor units connection