Daikin RQYQ16PY1 [170/194] Troubleshooting

Daikin RQYQ20PY1 [170/194] Troubleshooting
Troubleshooting by Remote Controller Si341009
161 Troubleshooting
Troubleshooting
NO
YES
Replace the outdoor unit main
PCB.
NO
YES
The number of indoor units
exceeds the allowable range.
Check the connection to correct.
Replace the outdoor unit main
PCB.
Match the refrigerant types of the
outdoor unit and the indoor unit.
Confirmation of error 3 Confirmation of error 4
Confirmation of error 3 Confirmation of error 4
Diagnosis Flow 1
Diagnosis Flow 2
The number
of indoor units connected
to the same refrigerant system
should not more than
64 units.
Check if
the refrigerant type of the
outdoor unit corresponds to
that of the indoor unit.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.