Daikin EUWAC5FZW [156/264] Inputs and outputs overview euwa 5 24kzw1 and euwy 5 24kzw1

Daikin EUWAC5FZW [156/264] Inputs and outputs overview euwa 5 24kzw1 and euwy 5 24kzw1
ESIE-0302 Inputs and Outputs Overview
Part 3 – Troubleshooting 3–5
33
4
5
1
1.3 Inputs and Outputs Overview: EUWA*5-24KZW1 and EUWY*5-24KZW1
Inputs/outputs The table below describes the relation between the wiring diagram symbols, the wiring connections
and the error codes.
For the exact location, see:
"PCB Layout of the EUWA*5-24KZW1 and EUWY*5-24KZW1" on page 1–97.
"Wiring Diagram: EUWA*5-24KZW1 and EUWY*5-24KZW1" on page 1–102.
Type Device
Wiring
diagram
symbol
Wiring con-
nection
terminal
Error code Description
Analog
input
Sensor R3T X1/B1-GND e1 - a1 Inlet water temperature sensor
R4T X1/B2-GND e2 (r6) Outlet water temperature sensor
Digital input Trans-
ducer
K4S + S1HP
+ QID
K5S + S2HP
+ Q2D
X1/ID3-GND h1 Overcurrent relay + high pressure switch +
discharge protector
S4LP/S5LP X1/ID4-GND l1 Low-pressure switch
Control
contacts
S9S (field) X1/ID5-GND (h7) Switch for remote start/stop
S7S (field) X1/ID2-GND (h6) Switch for remote cool/heat selection
S10L X1/ID1-GND (fl) Flow switch
Digital out-
put
K1M X2C1/2-NO1 Compressor 1 contactor
K2M X2C1/2-NO2 Compressor 2 contactor
K1P (field) X2C3/4-NO3 Pump contactor
Y1R/Y2R X2C3/4-NO3 Reversing valve
H1P (field) X2C5-NO5 Indication lamp alarm

Содержание

Скачать
Случайные обсуждения