Daikin EUWAC5FZW [24/264] The sound power level is an absolute value that does not depend on the surroundings or the distance it cannot be measured in the field iso 9614

Daikin EUWAC5FZW [24/264] The sound power level is an absolute value that does not depend on the surroundings or the distance it cannot be measured in the field iso 9614
ESIE-0302 General Outline
Part 1 – System Outline 1–15
3
1
4
5
(1)
: The table below contains the minimum water volume settings.
(2)
: The sound power level is an absolute value that does not depend on the surroundings or the
distance. It cannot be measured in the field (ISO 9614).
Pump
No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction
Model __ CH8-30 __ CH8-30
Nominal static
height pump
__ 243 kPa __ 210 kPa
Nominal static
height unit
__ 187 kPa __ 137 kPa
Hydraulic components
Buffer tank __ 55 l __ 55 l
Unit water volume 6 l 9 l 65 l 6 l 10 l 66 l
Expansion vessel __ 12 l __ 12 l
Pre-pressure
expansion vessel
1.5 bar
Safety valve __ 3 bar __ 3 bar
Dimensions
(h x w x d)
1321 x 2580 x 734 mm 1541 x 2580 x 734 mm
Weight
Machine weight 430 kg 448 kg 460 kg 490 kg 508 kg 520 kg
Operation weight 436 kg 457 kg 525 kg 496 kg 518 kg 586 kg
Casing
Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material Polyester coated galvanised steel plate
Sound power
level
(2)
79 dBA 81 dBA
Safety devices
Low-pressure switch
High-pressure switch
Pump motor overcurrent
Discharge temperature protection
Outlet water temperature protection
Compressor motor overcurrent relay
Fan thermal protector
Anti-recycling and guard timer
Digital display controller with electronic temperature control
Reverse phase protector
Flow switch.
Model EUWAN16KZW1 EUWAP16KZW1 EUWAB16KZW1 EUWAN20KZW1 EUWAP20KZW1 EUWAB20KZW1
Setting EUWA16-20KZW1
The minimum water volume for standard thermostat difference setting 3 K
For reduced setting multiply this water volume by 3/new setting
Minimum allowable setting 0.1 K