Daikin EUWAC5FZW [181/264] Items to be checked

Daikin EUWAC5FZW [181/264] Items to be checked
Troubleshooting ESIE-0302
3–30 Part 3 – Troubleshooting
3
1
3
4
5
4.2 Items to Be Checked
Introduction The tables below contain the most frequent failures and their corresponding corrective action:
In case the unit does not start and there is no malfunction indication.
In case the unit does not start and there is a malfunction indication.
No malfunction
indication
The unit does not start and there is no malfunction indication:
Malfunction
indication
The unit does not start and there is a malfunction indication:
Possible causes Items to be checked
Power supply problem:
Main supply
Control system supply
PCB supply (for EUWA*5-24KZW1
and EUWY*5-24KZW1)
Loose or broken connections
Blown fuses (due to short circuit)
Defective transformer
The unit is not switched ON.
Check the remote start/stop set-up and correct it, if
necessary.
In case of remote control, check the field wiring.
One of the timers is still active. Check the timers overview in this manual and wait
until all timers have elapsed. See ‘‘Compressor Tim-
ers” on page 2-10.
The unit is incorrectly programmed. Check the settings.
Do not set the compressor step in manual mode con-
trol to 0%.
Malfunction Possible causes Items to be checked
Freeze-up
Water flow too low
Refrigerant shortage
Operation out of range
Defective thermostat control
Pump operation
Water flow (blocked valves)
Flow switch operation
Operation condition
Blocked parts in the refrigerant system
Refrigerant leaks
Overcurrent in
the compressor
Failure on one of the phases
Low supply voltage
Motor overload
Power supply
Fuses
Mains isolator switch
Mains relay contacts
Operation condition
Compressor windings
Current on all 3 phases
Reset the overcurrent relay