ESIE-0302 Troubleshooting
Part 3 – Troubleshooting 3–31
33
4
5
1
An overview of the malfunction indications and safeties is given in "Malfunction Indications and
Safeties Overview" on page 3–9.
High-pressure
switch
Defective condenser fan
operation in cooling
Dirty or blocked condenser
Operation out of range
Operation condition
outdoor air temp. < 43˚C
State of the condenser (clean)
Flow switch or
pump contact
Damaged flow switch
Incorrect pump operation
Incorrect field wiring
Defective control devices
(pump relay)
Flow switch
Pump operation
Field wiring
Control devices
Discharge ther-
mal protector
Refrigerant shortage
Operation out of range
Refrigerant leak
Operation condition
Fan thermal
protector
Blocked fan
Blocked condenser
State of the fans (free rotation)
State of the condenser
Reverse phase
protection
Incorrect phase direction
One phase missing
Swap two phases
Connect the loose phase
Malfunction Possible causes Items to be checked