General Outline ESIE-0302
1–30 Part 1 – System Outline
3
1
1
4
5
(1)
: The table below contains the minimum water volume settings.
No. of circuits 2
Pump
No. x type __ 1 x Horizontal multi-stage end-suction
Model __ CH8-40
Nominal static height
pump
__ Cooling: 222 kPa
Heating: 199 kPa
Nominal static height
unit
__ Cooling: 146 kPa
Heating: 111 kPa
Hydraulic components
Buffer tank __ 55 l
Unit water volume 6 l 10 l 66 l
Expansion vessel __ 12 l
Pre-pressure
expansion vessel
1.5 bar
Safety valve __ 3 bar
Dimensions
(h x w x d)
Weight
Machine weight 516 kg 534 kg 546 kg
Operation weight 522 kg 544 kg 612 kg
Casing
Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material Polyester coated galvanised steel plate
Sound power level
(2)
81 dBA
Safety devices
Low-pressure switch
High-pressure switch
Pump motor overcurrent
Discharge temperature protection
Outlet water temperature protection
Compressor motor overcurrent relay
Fan thermal protector
Anti-recycling and guard timer
Digital display controller with electronic temperature control
Reverse phase protector
Flow switch.
Setting EUWY24KZW1
The minimum water volume for standard thermostat differ-
ence setting
3K
For reduced setting multiply this water volume by 3/new setting
Minimum allowable setting 0.1 K
Model EUWYN24KZW1 EUWYP24KZW1 EUWYB24KZW1