Test Run and Operation Data ESIE-0302
4–44 Part 4 – Commissioning and Test Run
3
1
4
5
2.2 Test Run and Operation Data for EUWAC5-10FZW1
Pressures The table below contains the measurable pressures.
Temperatures The table below contains the measurable temperatures.
Voltages The table below contains the measurable voltages.
Currents The table below contains the currents and used fuses.
Recommended fuses according to IEC standard 269-2: gL/gG (aM also admitted)
(F1U, F2U, F3U = gL/gG)
Measurement Value
Suction pressure 4 – 8.5 bar
Discharge pressure 7 – 22 bar
Maximum water pressure 10 bar
Measurement Value
Leaving water temperature
Standard: 4 – 20˚C
For ZH: -5 – 21˚C
For ZL: -10 – 21˚C
Outdoor temperature
-10 – 43˚C
Temperature difference at the air side 10 – 15˚C
Temperature difference at the water side 3 – 8˚C
Discharge temperature 80 – 120˚C
Measurement Value
Power supply voltage Within ± 10% of the rated voltage
Phase imbalance Within ± 2% of the rated voltage
Control circuit voltage 230 V AC for main electromagnetic switches
24 V DC for the controllers
Unit Nominal current Maximum current Fuses
EUWAC5FZW1 9 A 16.8 A 3 x 25 gG
EUWAC5FZW1 14 A 21.4 A 3 x 32 gG
EUWAC5FZW1 17 A 25.5 A 3 x 32 gG