Daikin EUWAC5FZW [210/264] Esie 0302 pre test run checks

Daikin EUWAC5FZW [210/264] Esie 0302 pre test run checks
ESIE-0302 Pre-Test Run Checks
Part 4 – Commissioning and Test Run 4–7
3
4
5
1
Calcium hardness mg CaCO
3
/l < 50 < 50 < 50 < 50 Scale
Silica ion mg SiO
2
/l < 30 < 30 < 30 < 30 Scale
Items to be referred to
Iron mg Fe/l < 1.0 < 0.3 < 1.0 < 0.3 Corrosion + scale
Copper mg Cu/l < 1.0 < 0.1 < 1.0 < 0.1 Corrosion
Sulphide ion
mg S
2-
/l
Not detectable Not detectable Not detectable Not detectable Corrosion
Ammonium ion
mg NH
4
+
/l
< 1.0 < 0.1 < 0.3 < 0.1 Corrosion
Remaining chloride mg Cl/l < 0.3 < 0.3 < 0.25 < 0.3 Corrosion
Free carbide mg CO
2
/l < 4.0 < 4.0 < 0.4 < 4.0 Corrosion
Stability index Corrosion + scale
Evaporator water Heated water (low temperature)
Tendency if out of
criteria