ESIE-0302 Malfunction Indications and Safeties Overview
Part 3 – Troubleshooting 3–13
33
4
5
1
What to do in the
event of an alarm
In the event of automatic reset, the system restarts automatically.
In the event of manual reset, proceed as follows:
Resetting warning
code n1
To reset warning code n1, proceed as follows:
After resetting the timer, carry out the required maintenance activities.
It is also possible to reset the timer cv, which defines the total running hours of the pump, in the
same way.
Step Action Result
1
Press
m.
The buzzer stops.
2 Find the cause of the alarm and correct it. The system has been repaired.
3 Reset the alarm manually by pressing the
u and d key simultaneously for ± 5 s.
The controller continues its normal opera-
tion, displaying the inlet water temperature.
Step Action
1
Enter the list of direct parameters by pressing the
s key for ± 5 s.
The parameter code r1 appears on the display.
2
Select parameter c9 using the
u and d key.
3
Press the
s key to choose the parameter and to switch to the parameter value.
4
Press the
u and d key simultaneously for approximately 5 s.
The timer’s value resets to 0.
5
Press the
s key to return to parameter code c9.
6
Press the
p key to return to normal operation.