Pre-Test Run Checks ESIE-0302
4–42 Part 4 – Commissioning and Test Run
3
1
4
5
Leak when in
heating mode
Check the operation conditions in the table below to find the cause of the malfunction.
The procedure to solve the problem is described in the last column.
See the illustration to situate the numbers in the table heading.
123456Cause Procedure
Hot Cool Hot as in
column
1
Cool as
in
column
1
Temper-
ature of
valve
body
Warmer
than
valve
body
The piston
needle is leaking
at the end of the
slide.
1. Operate the valve several
times.
2. Recheck.
3. If there is an excessive
leak, replace the valve.
Hot Cool Hot as in
column
1
Cool as
in
column
1
Warmer
than
valve
body
Warmer
than
valve
body
The piston
needle and pilot
needle are leak-
ing.
1. Operate the valve several
times.
2. Recheck.
3. If there is an excessive
leak, replace the valve.