ESIE-0302 Troubleshooting
Part 3 – Troubleshooting 3–35
33
4
5
1
Loading
parameters
To load parameters when you have entered the factory menu, proceed as follows:
To exit the factory
menu
To exit the factory menu when you have changed all parameters, proceed as follows:
Sensors The table below contains the settings of the sensors.
Step Action Result
1
Scroll using u or d to go to parameter HC.
2
Press
s.
3
Scroll using
u or d to change the value to 01.
4
Press
s.
You see parameter HC.
5
Scroll using
u or d to go to parameter H1.
You can start initialization.
6
Press
s.
7
Scroll using
u or d to change the value to 02.
8
Press
s.
You see parameter H1.
9
Use
u or d to go to the other parameters.
For the other parameters, see the tables further in this section:
Sensors
Regulator
Compressor
Fans
Anti-freeze and supporting heaters
Alarm
Others.
Step Action
1
Press
p.
2 Turn OFF the power supply.
Code Function EUWAC5-10FZ Read/write
13 Air coil or ambient probe type 0 r/w
16 Offset for /1 0˚C
17 Offset for /2
18 Offset for /3
1b Digital filter 4
1v Input limitation 8
1d Measurement unit 0