Daikin FTXS35G2V1B [130/319] Check no 5 refer to p 47

Daikin FTXS25G2V1B [130/319] Check no 5 refer to p 47
Troubleshooting SiBE04-808_B
119 Service Diagnosis
Troubleshooting
Check No.05
Refer to P.147
Check No.06
Refer to P.148
Check No.11
Refer to P.150
NG
OK
NO
OK
NG
OK
YES
NG
Correct it.
Reconnect it.
YES
YES
YES
NO
NO
Replace the outdoor unit
PCB.
Refrigerant shortage
Water mixed
Stop valve
Replace the defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
Reconnect in position.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R11710)
Four way valve coil
disconnected (loose)?
Harness out of connector?
Any thermistor
disconnected?
Check No. 06
Check the thermistors.
Check No. 11
Check the refrigerant
line.
Check No. 05
Check the four way valve
switching output.
Check the continuity of the four way
valve coil and harness.
Replace the four way valve
coil.
NO
Resistance
between harnesses about
1000 ~ 2000 ?
Disconnect the harness from the
connector.