Daikin FTXS35G2V1B [53/319] Inverter powerful operation

Daikin FTXS50G2V1B [53/319] Inverter powerful operation
SiBE04-808_B Main Functions
Function and Control 42
1.11 Inverter POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Detail When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
Ex.) : POWERFUL operation in cooling mode.
Operation mode Fan speed Target temperature
COOL H tap + 50 rpm 18°C
DRY Dry rotating speed + 50 rpm Lowered by 2.5°C
HEAT H tap + 50 rpm 31°C
FAN H tap + 50 rpm
AUTO Same as cooling / heating in
POWERFUL operation
The target temperature is
kept unchanged.
(R7096)
Target temp.
Fan
50 rpm
18˚C
H tap
Set tap
20 minutes
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
It should be the lower limit of
cooling temperature.
It counts 20 minutes. also
in the remote controller.
POWERFUL
ON
POWERFUL
OFF