Daikin RXYQ14MAY1 [104/352] Pressure equalization prior to startup

Daikin RXYQ16MAY1 [104/352] Pressure equalization prior to startup
SiE39-407 Special Control
Function 93
3.7 Pressure Equalization prior to Startup
Actuator Operation Remarks
Compressor OFF
Outdoor unit fan
Cooling:OFF
Heating:STEP 4
Four way valve Holds ON
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF In the case of RXYQ5M, this valve turns ON.
Receiver gas discharging valve
(SVG)
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
OFF
Ending conditions 10 sec.
In the case of RXYQ5MA, 3 min. or Pc
-
Pe<0.2
MPa