SiE39-407 Troubleshooting by Remote Controller
Troubleshooting 179
Outdoor
Unit
LA 999Malfunction of power unit
LC 999Malfunction of transmission between inverter and
control PC board
222
P1 999Inverter over-ripple protection 224
P4 999Malfunction of inverter radiating fin temperature rise
sensor
225
System U0 879Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
226
U1 999Reverse phase / open phase 227
U2 999Power supply insufficient or instantaneous failure 228
U3 999Check operation is not conducted. 230
U4 999Malfunction of transmission between indoor and
outdoor units
231
U5 999Malfunction of transmission between remote
controller and indoor unit
233
U5 787Failure of remote controller PC board or setting
during control by remote controller
233
U7 999Malfunction of transmission between outdoor units 234
U8 997Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
236
U9 999Malfunction of transmission between indoor unit and
outdoor unit in the same system
237
UA 999Excessive number of indoor units etc. 239
UC 888Address duplication of central remote controller 240
UE 999Malfunction of transmission between central remote
controller and indoor unit
241
245
251
UF 999Refrigerant system not set, incompatible wiring /
piping
243
UH 999Malfunction of system, refrigerant system address
undefined
244
Centralized
Control
and
Schedule
Timer
M1 8 or 79 9PC board defect 246
253
M8 8 or 79 9Malfunction of transmission between optional
controllers for centralized control
247
254
MA 8 or 79 9Improper combination of optional controllers for
centralized control
248
255
MC 8 or 79 9Address duplication, improper setting 250
257
Heat
Reclaim
Ventilation
64 879Indoor unit’s air thermistor error
65 879Outside air thermistor error
68 879
6A 879Damper system alarm
6A 999Damper system + thermistor error
6F 879Malfunction of simple remote controller
6H 879Malfunction of door switch or connector
94 999Internal transmission error
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.