Daikin RXYQ14MAY1 [306/352] Fxuq71m 100m 125mv1

Daikin RXYQ10MAY1 [306/352] Fxuq71m 100m 125mv1
SiE39-407 Wiring Diagrams for Reference
Appendix 295
FXUQ71M / 100M / 125MV1
3D044973
A1P
A2P
C1
HAP
HBP
M1S
M1F
M1P
Q1M
R1T
R2T
RyA
RyP
S1Q
S1L
SS1
V1TR
X1M
X2M
RC
TC
Printed circuit board
Printed circuit board
(Transformer 220-240V/16V)
Capacitor (M1F)
Light emitting diode
(Service monitor green)
Light emitting diode
(Service monitor green)
Motor (Swing flap)
Motor (Indoor fan)
Motor (Drain pump)
Thermo switch (M1F embedded)
Thermistor (Air)
Thermistor (Coil)
Magnetic relay (M1A)
Magnetic relay (M1P)
Limit switch (Swing flap)
Float switch
Selector switch (Emergency)
Phase control circuit
Terminal strip
Terminal strip
Signal receiver
Signal transmission circuit
Indoor unit
R1T
SS1
A3P
A4P
BS1
H1P
H2P
H3P
H4P
SS1
SS2
X24A
X30A
X35A
Thermistor (Air)
Selector switch (Main/sub)
Printed circuit board
Printed circuit board
Push button (On/off)
Light emitting diode
(On-red)
Light emitting diode
(Timer-green)
Light emitting diode
(Filter sign-red)
Light emitting diode
(Defrost-orange)
Selector switch (Main/sub)
Selector switch
(Wireless address set)
Connector (infrared remote control)
Connector (interface
adaptor for sky air series)
Connector (Group control adaptor)
Wired remote control
Receiver/display unit (attached to
infrared remote control)
Connector for optional parts
POWER SUPPLY
50
~
220-240V
Notes:
1. : Terminal,
: Connector
2. : Field wiring
3. The BEV unit shows an outline, please refer to a wiring diagram
of BEV unit pasting in detail.
4. In case using central remote control, connect it to the unit in
accordance with the attached installation manual.
5. X24A is connected when the infrared remote control kit is being used.
6. Remote control model varies according to the combination system, confirm engineering materials
and catalogs, etc. b
efore connecting.
7. Confirm the method of setting the selector switch (SS1, SS2) of wired remote control and infrared
remote control by installation manual and engineering data, etc.
8. Symbols show as follows: RED: red, BLK: black, WHT: white, YLW: yellow, GRN: green, BLU: blue.
Wired remote
control
Control box
Note 5
Note 5
Indoor unit
BEV unit
Receiver/display unit
Note 3