Daikin RXYQ14MAY1 [141/352] Outdoor air processing unit field setting remote controller

Daikin RXYQ36MAY1 [141/352] Outdoor air processing unit field setting remote controller
Field Setting SiE39-407
130 Test Operation
3.1.7 Outdoor Air Processing Unit-Field Setting (Remote Controller)
Note) Bold face in indicates the default setting.
Mode
No.
Setting
SW
No.
Setting
contents
Setting position No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
10
(20)
0 Stain of filter 2500hr 1250hr —————————————
3
Filtering
time
cumulation
Display
No
display
—————————————
12
(22)
1
External
ON/OFF
input
Forced
stop
ON-OFF
control
—————————————
5
Power
failure
automatic
reset
Not
equipped
Equipped
—————————————
14
(24)
3
Discharge
temperature
(cooling)
13°C 14 15 16 17 18 19 20 21 22 23 24 25 25 25
4
Discharge
temperature
(heating)
18°C 19 20 21 22 23 24 25 26 27 28 29 30 30 30