148 Test Operation
d Set Cool / Heat Separately for Each Outdoor Unit System by Cool/Heat Switching Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to “outdoor” (factory set).
Set cool/heat switching to “individual” for “Setting mode 1” (factory set).
MODE
IND
H1P H2P H3P H4P H5P H6P H7P
SLAVE
C/H SELECT
C/H SELECT
C/H SELECT R.C.
Indoor unit
C/H select
remote
control
F1 • F2
Indoor unit
(V3059)
F1 • F2
I-O
ABCF1F2F1F2Q1Q2
O-O OUT-MULTI
Dip SW.
DS1-1
O
I
MASTER
L.N.O.P. DEMAND
TEST
MALFNC.