SiE39-407 Troubleshooting by Indication on the Remote Controller
Troubleshooting 185
Troubleshooting
(V2778)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace float switch.
Modify the float switch's
connection and turn on again.
Connect the drain pump and
turn on again.
Check the drain piping for
clogging or upward slope, etc.
Replace indoor unit PC board.
Replace the drain pump or
check for dirt, etc.
Connect either a short circuit
connector or float switch and
turn on again.
YES
YES
YES
YES
Defect of indoor unit PC board.
Loo
se connection of connector.
NO NO
NO
YES
YES
NO
NO
YES
NO
YES
NO
NO
NO
Provide 220~240V power
supply.
YES
NO
Is power supply
220~240V provided?
The float
switch is connected to
X8A of the indoor unit
PC board.
The float
switch contact is
forming a short circuit
(continuity check
with X8A or X15A
disconnected)
Water builds up
in the drain pan.
The drain
pump is connected
to X25A or terminal
s Y1
and Y2 of the
indoorunit PC
board.
The drain
pump works when
the power supply is reset
for the indoor
unit.
The voltage
of terminals Y1
and Y2 or X25A is
220~240 V (within
5 minutes of resetting
the power
supply).
A short
circuit connector is
connected to
X8A.
Becomes
normal when X8A of
the indoor unit PC board
is short circuited
The float switch
functions normally.