Daikin RXYQ14MAY1 [171/352] Setting of refrigerant recovery mode

Daikin RXYQ22MAY1 [171/352] Setting of refrigerant recovery mode
Field Setting SiE39-407
160 Test Operation
[Operation procedure detail]
c After turning the respective remote switch of indoor and outdoor units off and charging the
refrigerant, turn on the power of indoor and outdoor units.
Do not fail to turn the power off and charge the refrigerant with outdoor unit in stop mode
before adding the refrigerant following this procedure, otherwise resulting in trouble.
d Fully open the stop valve on the gas side and oil equalizing valve for multi outdoor
connection, and do not fail to fully close the stop valve on the liquid side. (If the stop valve on
the liquid side is open, the refrigerant cannot be charged.)
e With the outdoor unit in the stopper state, while in Setting mode 2 (H1P: ON), set (A)
Refrigerant refilling operation (set item No. 20) to "ON", thus initiating the operation. (The
H2P will blink to indicate "Test Operation", and then "TEST OPERATION" and "UNDER
CENTRALIZED CONTROL" will be displayed on the remote controller.
f When the refrigerant is charged up to the specified amount, press the RETURN button
(BS3) to stop charging.
The charging operation is automatically stopped after operating for a maximum of about 30
minutes.
If the refrigerant refilling is not completed within a period of 30 minutes, make setting of (A)
Refrigerant refilling operation (set item No. 20) again and then start the operation.
When the charging immediately stops even by restarting, the refrigerant is charged
excessively. The refrigerant cannot be charged any more.
g Do not fail to fully open the stop valve on the liquid side as soon as disconnecting the
refrigerant charging hose.
(The piping may be burst due to the liquid sealing.)
[Operation state]
Compressor frequency : 210Hz
Y1S, Y2S Solenoid valve : Open
Outdoor unit fan : High pressure control
Indoor unit expansion valve (All unit) : 1024 pulse
Indoor unit fan : H tap
3.2.5 Setting of Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective expansion valve of
indoor and outdoor units
[Operation procedure]
c In setting mode 2 with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. (H2P
turns to display “TEST OPERATION” (blinks), “TEST OPERATION” and “IN CENTRALIZED
CONTROL” are displayed on the remote controller, and the operation is prohibited.
d Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
e Press Mode button “BS1” once and reset “Setting Mode 2”.