Daikin RXYQ14MAY1 [240/352] Troubleshooting

Daikin RXYQ8MAY1 [240/352] Troubleshooting
SiE39-407 Troubleshooting by Indication on the Remote Controller
Troubleshooting 229
Troubleshooting
(V2821)
Replace K1M.
Repair wiring.
NO
NO
NO
Turn on again.
Replace the outdoor unit
PC board (A1P).
YES
YES
YES
Turn K1M ON.
YES
NO
Is
220 ~ 240 V of
power reaching the
K1M coil?
Is
220 ~ 240 V
at the connector X1A of
inverter PC
board.
Replace the inverter PC
board.
Replace the inverter PC
board.
YES
NO
NO
Does
the voltage
between terminals
P2(or P3) and N3 gradually
rise to 556 VDC (Y1)
after turning
on?
Monitor field power
supply.
Replace the inverter
PC board.
The voltage
between the P2
(or P3) and N3 terminals
is 380 VDC (Y1) or
more when the
compressor is
running.
Is
connection
wire connected
between the connector
X21A and X6A?
YES
NO
Is
220 ~ 240 V
at the connector X1A of
outdoor PC board
side?
Check the transmission
wiring between the
outdoor unit PC board
and inverter unit.
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.