A push button is placed on a door of the unit electrical panel. The button is highlighted by a red color in
yellow background. A manual pressure of the emergency stop button stops all loads from rotating, thus
preventing any accident which may occur. An alarm is also generated by the Unit Controller. Releasing the
emergency stop button enables the unit, which may be restarted only after the alarm has been cleared on
the controller.
The emergency stop causes all motors to stop, but does not switch off power to the
unit. Do not service or operate on the unit without having switched off the main
switch.
1.3.2 Circuit safety devices
Safety of this level of severity will shut down the circuit they protect. The remaining circuits will keep
running.
1.3.3 Component safety devices
Safety of this level of severity will shut down a component against abnormal running condition that could
create permanent damages to it. An overview of the protecting devices is listed below:
Overcurrent/Overload Protections
Overcurrent/overload devices protect electrical motors used on compressors, fans and pumps in case
of overload or short circuit. In case of inverter-driven motors, overload and overcurrent protection is
integrated in the electronic drives. A further protection from short circuit is accomplished by fuses or
circuit breakers installed upstream each load or group of loads.
Overtemperature Protections
Fan electrical motors are also protected from overheating by thermistors immersed into motor
windings. Should the winding temperature exceed a fixed threshold, the thermistors will trip and
cause the motor to stop.
Do not operate on a faulty fan before the main switch has been shut off.
Overtemperature protection is auto-reset, therefore a fan may restart automatically if
temperature conditions allow it.
Phase reversal, under/over voltage, ground fault protections
When one of those alarms occurs the unit is immediately stopped or even inhibited to start. The
alarms clear automatically once the problem is fixed. This auto clear logic allows the unit to
automatically recover in case of temporary conditions where the supply voltage reaches the upper or
lower limit set on the protection device. In the other two cases a manual intervention on the unit will
be required in order to solve the problem. In case of a phase reversal alarm two phases requires to be
inverted.
In the event of a power supply outage, the unit will restart automatically without the need for an
external command. However, any faults active when the supply is interrupted are saved and may in
certain cases prevent a circuit or unit from restarting.