Daikin EWAQ340GZXR [46/78] Pump freeze protection

D-EOMHP00706-14EN - 46/78
7.1.2.4 Pump freeze protection
[Purpose]
Avoid water freezing. If water temperature goes down to below set point pump should be started
regardless chiller operation.
[Trigger]
EWT or LWT is less than Water freeze set point 0.6°C when unit is off.
[Action]
Start pump
[Reset]
Auto clear when trigger conditions no longer exist. As well pump should be turned off.
7.1.2.5 Pump hot water protection
[Purpose]
Keep system in safety. If water temperature goes up to over set point pump should be stopped regardless
chiller operation.
[Trigger]
EWT of LWT is more than 65°C when pump is running.
[Action]
Stop pump
[Reset]
Auto clear when trigger conditions no longer exist. As well pump can be turned on if needed.
7.1.2.6 Water temp inverted
[Purpose]
Detect wiring mistake. Keep LWT control in right operation.
[Trigger]
Water temperature is inverted compared to expectation.
[Action]
Normal shutdown (pumpdown) of all running circuits
[Reset]
This alarm can be cleared manually via the keypad or via BAS command if trigger conditions no longer
exists.