6 Unit functions
6.1 LWT target setting
The follows define the how to set or reset the LWT target by Local or Network control.
6.1.1 LWT target
--- For Heat pump Unit ---
If Unit type set point is set to “Heat pump” the Base LWT target shall be set according to the table below.
Available
Modes Set
Point
Control
Source Set
Point
Heat/Cool
switch
Mode Input
BAS req
Base LWT Target
Cool / Heat
Local
Cool
OFF
x
Cool LWT 1
ON
x
Cool LWT 2
Heat
OFF
x
Heat LWT 1
ON
x
Heat LWT 2
Network
x
Cool
BAS Cool set point
Heat
BAS Heat set point
Cool / Heat /
Ice w/Glycol
Local
Cool
OFF
x
Cool LWT 1
ON
x
Ice LWT
Heat
OFF
x
Heat LWT 1
ON
x
Heat LWT 2
Network
x
Cool
BAS Cool set point
Ice
BAS Ice set point
Heat
BAS Heat set point
Note: “x” indicates that the value is ignored.
--- For Cooling Unit ---
If Unit type set point is set to “Cooling” the Base LWT target shall be set according to the table below.
Available Modes
Set Point
Control Source
Set Point
Mode Input
BAS req
Base LWT Target
Cool
Local
OFF
x
Cool LWT 1
ON
x
Cool LWT 2
Network
x
x
BAS Cool set point
Cool w/Glycol
Local
OFF
x
Cool LWT 1
ON
x
Cool LWT 2
Network
x
x
BAS Cool set point
Cool / Ice w/Glycol
Local
OFF
x
Cool LWT 1
ON
x
Ice LWT
Network
x
Cool
BAS Cool set point
Ice
BAS Ice set point
Ice w/Glycol
Local
x
x
Ice LWT
Network
x
x
BAS Ice set point
Note: “x” indicates that the value is ignored.
6.1.2 LWT target resetting
The base LWT target may be reset and it is configured for a reset. The type of reset to be used is
determined by the LWT Reset Type set point. After resets are applied, the LWT target can never exceed a
value of 20°C in cooling and never fall short of a value of 25°C in heating mode. Target will be reset every
10seconds with each 0.1°C.