Daikin EWAQ340GZXR [52/78] Low evaporator pressure shutdown

D-EOMHP00706-14EN - 52/78
This alarm can be cleared manually via the keypad if HPS digital input is closed.
7.2.2.3 High Condenser Pressure Shutdown
[Purpose]
To avoid the circuit triggers HPS fault alarm.
[Triggers, Actions and Resets]
The Circuit takes rapid shutdown when the condenser pressure becomes higher than the limit. The
Circuit takes unload or inhibit load sequence before it goes over the limit. Shutdown requires reset
manually. Unload and inhibit load is reset automatically when conditions are recovered.
7.2.2.4 Low Evaporator Pressure Shutdown
[Purpose]
To protect compressor in case of that refrigerant charge is less or refrigerant tube is closed due to some
problems. This alarm could work in heating mode. In case of cooling mode Low evaporator gas
temperature alarm may be triggered before this alarm.
[Alarm type]
Fault
[Triggers, Actions and Resets]
The Circuit takes rapid shutdown when the evaporator pressure becomes lower than the limit. The
Circuit takes unload or inhibit load sequence before it goes under the limit. Shutdown requires reset
manually. Unload and inhibit load is reset automatically when conditions are recovered.
7.2.2.5 Low Evap Gas Temperature freeze Shutdown
[Trigger]
Evaporator Gas temperature is less than limit when Circuit is running in cooling cycle
[Alarm type]
Fault
[Action]
Rapid shut down of running circuit
[Reset]
This alarm can be cleared manually via the keypad or via BAS command if the trigger condition no longer
exists.
7.2.2.6 High Pressure Ratio Shutdown
[Purpose]
Protect scroll parts of compressor.
[Alarm type]
Fault