Daikin EWAQ340GZXR [22/78] Setpoint override

D-EOMHP00706-14EN - 22/78
The demand limit signal can be changed continuously between 4 and 20 mA. The Microtech III will
convert this signal into a unit capacity limitation changing between minimum capacity and full capacity
with a linear relationship. A signal between 0 and 4mA will correspond to a full unit capacity. In this way
if nothing is connected to this input no limitation will be applied. The maximum limitation will never
force a unit shutdown.
3.6.1.12 Setpoint override
This input allows applying an offset on the Active Setpoint to adjust the operating point of the ELWT. This
input can be used to maximize the comfort.