D-EOMHP00706-14EN - 21/78
Operating the unit by-passing the flow switch input or without an appropriate flow
switch may damage the evaporator due to freezing. Operation of the flow switch must be
checked prior to start up the unit.
3.6.1.2 Double setpoint
This contact can be used to switch between two different LWT setpoints and depending on the
application between different modes of operation.
3.6.1.3 Current limit (optional)
This optional feature enables a capacity control of the unit in order to limit the input current. The current
limit feature is included in the Energy Meter option. The limiting signal will be compared with a limiting
value set on the HMI. By default the current limit setpoint is selected through the HMI; an external 4-20
mA signal can be enabled to allow a remotely changeable setpoint.
3.6.1.4 External Fault
This contact is available to report to the UC a fault or a warning from an external device. It could be an
alarm coming from an external pump to inform the UC of the fault. This input can be configured as a fault
(unit stop) or a warning (displayed on the HMI).
Ice operation must be selected in case of ice storage application. In this case the UC will run the chiller in
on/off mode switching all chillers off as soon as the setpoint is reached. In this case the unit will run to
full capacity and then will switch off applying an ice delay different chiller starts.
3.6.1.5 Rapid Restart (optional)
Purpose of the rapid restart feature is to let the unit restart in the shortest possible time after a power
failure, and then recover in the shortest possible time (maintaining the reliability level of the normal
operations) the capacity it had before the power failure. The rapid restart is enabled by the enable switch.
3.6.1.6 Remote On-Off
This unit can be started through a remote enable contact. The Q0 switch must be selected to “Remote”.
3.6.1.7 General Alarm
In case of a unit alarm, this output is closed thus indicating a fault condition to an externally connected
BMS.
3.6.1.8 Compressor Status
The digital output is closed when the related circuit is in run state.
3.6.1.9 Alarm Circuit (optional)
This option is included with the “Rapid Restart” option. The related digital contact is closed in case of
alarm on a circuit.
3.6.1.10 Evaporator Pump Start
A 24 Vdc digital output (with internal supply) is enabled when a pump (#1 or #2) is required to start. The
output can be used to start an external pump (either at fixed or variable speed). The output requires an
external input or a relay with less than 20 mA excitation current.
3.6.1.11 Demand limit
This optional function can be used to limit the unit capacity percentage to a changeable limit value. This
limitation cannot be directly linked to a corresponding limitation of the unit current (50% demand limit
can differ from 50% of the unit FLA).