Daikin EWAQ340GZXR [16/78] Light emitting diodes on boards

Daikin EWYQ380GZXS [16/78] Light emitting diodes on boards
D-EOMHP00706-14EN - 16/78
3.3 Light emitting diodes on boards
All boards continuously check and indicate the proper operation of their electronic circuits. A light
emitting diode (LED) lights on the UC and two additional lights on each extension board when it is
operating properly.
3.3.1 UC BSP LED
Mode
LED
BSP initialization. This indicates the startup and preparation of all files.
After this mode the final run mode (bellow) is active. Available since VVS10.
Green flashing with 50ms on and 1000ms off
BSP upgrade mode in progress
Per second flashing between red and green.
Application not loaded
Yellow flashing with 50ms on and 1000ms off
Application loaded but not running or BSP Upgrade mode active
Yellow
Application running
Green
BSP error (software error)
Red flashing with 2Hz
Hardware error
Red
Fail safe mode (in case that the BSP upgrade was interrupted)
Yellow with Red flashing every second for 500ms
(since VVS10) BSP startup phase. The controller needs time for starting.
Green flashing with 50ms on and 1000ms off
BAS interface
MicroTech III main controller
POL687
I/O extension POL965
(Address: 18)
I/O extension POL965
(Address: 2)
I/O extension POL94U
(Address: 3)
I/O extension POL965
(Address: 4)
I/O extension POL965
(Address: 22)
I/O extension POL94U
(Address: 5)
ACS I/F board: A301P
(Rotary Switch: 0)
Compressor VFD
(Address: 1)
Compressor VFD
(Address: 2)
Compressor VFD
(Address: 1)
Compressor VFD
(Address: 1)
Compressor VFD
(Address: 1)
Compressor VFD
(Address: 2)
Compressor VFD
(Address: 2)
Compressor VFD
(Address: 2)