8.7 Soft load control
8.7.1 Unit setting
Soft Loading is a configurable function used to ramp up the unit capacity over a given time. The set points
that control this function are:
1) Soft Load (ON/OFF)
2) Begin Capacity Limit (Unit %)
3) Soft Load Ramp (seconds)
This control can be enabled during normal operation. But this will be active at next start.
8.7.2 Soft load control
‘Soft load unit limit increases linearly from the Begin Capacity Limit set-point to 100% over the amount
of time specified by the Soft Load Ramp set-point.
If the option is turned off, the soft load limit is set to 100%.
8.7.3 Soft load control with 56rps start
If the 56rps start is required the begin capacity limit will be ignored. In that case Soft load unit limit
increases linearly from 56rps to 100% over the amount of Soft load ramp time. Concerning 56rps start,
see compressor control section.
8.7.4 Soft load control during defrost
This function shall be ignored during defrost operation.
8.8 Fan VFD control
8.8.1 Unit setting
Fan VFD should be enabled only when the Fan VFD configuration is set to enable.
8.8.2 Fan control with VFD
Condenser pressure or evaporator pressure trim control is accomplished using an optional VFD on the
first fan. This VFD control should vary the fan speed to drive the saturated condenser or evaporator
temperature to a target value.
8.9 Liquid line solenoid valve
8.9.1 Unit setting
If the unit has a liquid line solenoid valve unit configuration must be set to enable.
8.9.2 Liquid line solenoid valve control
Liquid line solenoid valve should be close when circuit state is off. Otherwise it should be open.