Daikin EWAQ340GZXR [76/78] Calculations

D-EOMHP00706-14EN - 76/78
10 Calculations
10.1 Refrigerant Saturated temperature
Refrigerant saturated temperature (Tc and Te) shall be calculated from the pressure sensor readings for
each circuit. A function will provide the converted value of temperature.
10.2 Suction Superheat
SSH shall be calculated for each circuit by the following equation.
SSH = Suct. Temp Te
10.3 Discharge Superheat
DSH shall be calculated for each compressor by the following equation.
DSH = Disch. Temp Tc
10.4 Evaporator Approach, Condenser Approach
Evaporator approach and condenser approach shall be calculated for each circuit.
10.4.1 At cooling mode
Condenser Approach = Tc OAT
Evaporator Approach = (EWT LWT) / Ln ((EWT Te) / (LWT Te))
Note: If EWT = LWT or LWT = Te, then Evaporator approach = 0
10.4.2 At heating mode
Condenser Approach = (LWT EWT) / Ln ((Tc EWT) / (Tc LWT)
Evaporator Approach = OAT Te
Note: If EWT = LWT or LWT = Tc, then Condenser approach = 0
10.5 Pressure Differential
Pressure differential shall be calculated for each circuit.
Pressure differential = Cond. Pr Evap. Pr
10.6 Pressure ratio
Pressure ratio shall be calculated for each circuit.
Pressure ratio = (Cond. Pr +101.325) / (Evap. Pr + 101.325)