Daikin EWAQ340GZXR [47/78] Low oat lock out

D-EOMHP00706-14EN - 47/78
7.1.2.7 Low OAT lock out
This alarm has two actions to be taken, which vary based on triggers. Also the set points are varied based
on Fan VFD configuration and circuit operation mode.
[Purpose]
Avoid a unit operates outside of operational envelope.
[Alarm type]
Trigger1 --- Fault
Trigger2 --- Warning
[Trigger 1]
OAT is less than low OAT lockout set point value for 20 minutes when unit is running.
[Trigger 2]
OAT is less than low OAT lockout set point value for 5seconds when unit is off. However, this alarm
shouldnt be triggered if OAT is out of range.
[Action]
If active via trigger 1:
Normal shutdown of all running circuits as fault
If active via trigger 2:
Not allow to start (Warning)
[Reset]
Auto clear when OAT becomes more than Low OAT lockout set point +2.5°C
7.1.2.8 High OAT lock out
This alarm has two actions to be taken, which vary based on triggers. This alarm can be active only when
chiller operates in heating mode.
[Purpose]
Avoid a unit operates outside of operational envelope.
[Alarm type]
Trigger1 --- Fault
Trigger2 --- Warning
[Trigger 1]
OAT is more than high OAT lockout set point value for 20 minutes only when unit is running in heating
mode.
[Trigger 2]
OAT is more than high OAT lockout set point value for 5seconds only when unit is off in heating mode.
[Action]
If active via trigger 1:
Normal shutdown of all running circuits as fault