Daikin EWAQ340GZXR [54/78] Evaporator pressure sensor fault

D-EOMHP00706-14EN - 54/78
[Action]
Rapid shutdown of circuit
[Reset]
This alarm can be cleared manually via the keypad or via BAS command if the sensor is back in range for
5seconds.
7.2.2.11 Evaporator pressure sensor fault
[Trigger]
Out of range for 1second
[Action]
Rapid shutdown of circuit
[Reset]
This alarm can be cleared manually via the keypad or via BAS command if the sensor is back in range for
5seconds.
7.2.2.12 Deicer temperature sensor fault
[Trigger 1]
Out of range for 1seconds when Circuit is running in cooling cycle
[Trigger 2]
Out of range for 1seconds when Circuit is running in heating cycle
[Action]
If active via trigger 1:
None (Warning only)
If active via trigger 2:
Rapid shutdown of circuit
[Reset]
If active via trigger 1:
Auto clear if the sensor is back in range for 5seconds.
If active via trigger 2:
This alarm can be cleared manually via the keypad or via BAS command if the sensor is back in
range for 5seconds.
7.2.2.13 Suction temperature sensor fault
[Trigger]
Out of range for 1second
[Action]
Rapid shutdown of circuit
[Reset]
This alarm can be cleared manually via the keypad or via BAS command if the sensor is back in range for
5seconds.