5 Unit availability
5.1 Unit enabling
Enabling and disabling the run command is accomplished using set points and inputs to the chiller. The
unit switch, remote switch input, and unit enable set point all are required to be “on” or enable for the
unit to be enabled when the control source is set to local. The same is true if the control source is set to
network, with the additional requirement that the BAS enable set point must be enabled. The table below
shows how to set the switches and set points for enabling unit run command.
Unit switch
Control source
set point
Remote switch
Unit enable
set point
BAS enable
set point
Unit enable
OFF
x
x
x
x
Disable
x
x
OFF
x
x
Disable
x
x
x
Disable
x
Disable
ON
Local
ON
Enable
x
Enable
x
Network
x
x
Disable
Disable
ON
Network
ON
Enable
Enable
Enable
Note: “x” indicates that the value is ignored.
5.2 Unit mode selection
Unit mode can be set according to the following table. If the mode change is occurred during operation
the chiller will stop at once, then restart in required mode. Test mode can be enabled only if the unit is off.
5.2.1 Heat pump chillers
Unit type
set point
Available
modes
set point
Control
source
set point
Mode input
BAS req.
Unit mode
Heat pump
Cool / Heat
Local
x
x
Cool
x
x
Heat
Network
x
Cool
Cool
Heat
Heat
Cool / Heat /
Ice with
Glycol
Local
OFF
x
Cool with Glycol
ON
x
Ice with Glycol
x
x
Heat with Glycol
Network
x
Cool
Cool with Glycol
Ice
Ice with Glycol
Heat
Heat with Glycol
x
Test
x
x
x
Test
Note1: “x” indicates those settings can be ignored.
Note2: Heat / Cool switch needs 3seconds to make sure Heat or Cool state when it’s changed.
5.2.2 Cooling chillers
Unit type
set point
Available
modes
set point
Control
source
set point
Mode input
BAS req.
Unit mode
Cooling
Cool
x
x
x
Cool
Cool with
Glycol
x
x
x
Cool with Glycol
Cool / Ice
Local
OFF
x
Cool with Glycol