Daikin EWAQ340GZXR [44/78] Unit fault alarms

D-EOMHP00706-14EN - 44/78
7.1.2 Unit fault alarms
7.1.2.1 Phase Volts loss / GFP fault
[Purpose]
Checking inverted phase, lack of phase and imbalance voltage.
[Trigger]
PVM / GFP input is low
[Action]
Rapid shutdown of all running circuits
[Reset]
Auto reset when PVM input is high or PVM set point does not equal single point for at least 5 seconds.
7.1.2.2 Water freeze shut down
[Purpose]
Reduce the risk of damage to chiller due to freeze.
[Trigger]
EWT or LWT is less than 2.8°C for 5second
[Action]
Rapid shutdown of all running circuits
[Reset]
This alarm can be cleared manually via the keypad or via BAS command if trigger conditions no longer
exists.
7.1.2.3 Water flow loss
[Purpose]
Reduce the risk of damage to chiller due to freeze or unstable condition.
[Trigger 1]
Flow switch is open for 15seconds
[Trigger 2]
Pump is running, but flow switch is open for 3minutes
[Action]
Rapid shutdown of all running circuits
[Reset]
This alarm can be cleared at any time manually via the keypad or via the BAS clear alarm command.
If active via trigger 1: