4.3 Basic settings
Before starting up the unit, some basic settings need to be done. These set points can be accessed via the
following path.
Menu Level 1
Menu Level 2
ENTER PASSWORD
Unit overview information
QUCIK MENU
VIEW / SET UNIT
VIEW / SET CIRCUIT
COMMISSION UNIT
--->
CONFIGURATION
CTRLR IP SETUP
LON SETUP
BACNET IP SETUP
BACNET MSTP SETUP
MODBUS SETUP
AWM SETUP
MENU PASSWORD
TIME UNTIL RESTART
ALARMS
SCHEDULED MAINTENANCE
ABOUT THIS CHILLER
DATA / TIME
4.3.1 Chiller configuration setting
Generally this setting has been done in the factory. However, chiller configuration settings must be set via
HMI keypad when the new software is installed. Unless setting all configurations the chiller will not be
able to start.
Contents
Selectable values
Note
Voltage
200~220, 220~230, 380,
400, 460
Frequency
50, 60
Unit type
Cool only, Heat pump
Efficiency type
Std Eff, Hi Eff
Number of Ckt
1,2
Number of comps
3, 4, 5, 6
Need to be set for each circuits
Number of fans
3, 4, 5
Need to be set for each circuits
Fan VFD
Enable, Disable
Liquid line SV
Enable, Disable
HPS setting
Normal, Higher limit
Higher limit will be used only