Daikin EWAQ340GZXR [73/78] D eomhp00706 14en 73 78

Daikin EWAQ320GZXR [73/78] D eomhp00706 14en 73 78
D-EOMHP00706-14EN - 73/78
Cool LWT 2
Unit
°C
7.0
4.0
20.0
Cool LWT 1
Unit
°C
7.0
-8.0
20.0
With glycol
Cool LWT 2
Unit
°C
7.0
-8.0
20.0
With glycol
Heat LWT 1
Unit
°C
45.0
25.0
50.0
Heat LWT 2
Unit
°C
45.0
25.0
50.0
Ice LWT
Unit
°C
-4.0
-8.0
4.0
Start up delta T
Unit
°C
2.7
0.0
5.0
Stage up delta T
Unit
°C
0.5
0.0
2.0
Stage down delta T
Unit
°C
0.8
0.0
1.7
Shut down delta T
Unit
°C
1.5
0.0
1.7
Nominal water delta T
Unit
°C
5.0
4.0
8.0
EWT max pulldown rate
Unit
°C/min
3.0
2.0
6.0
Stage up tm
Unit
Min.
3
0
60
Ice delay timer
Unit
Hrs
12
1
23
Light load stage down
Unit
%
35
20
50
High load stage up
Unit
%
80
50
100
LWT reset type
Unit
-
None
None, 4-20mA, Return,
OAT
Max Reset
Unit
°C
5.0
0.0
10.0
Start Reset Delta T
Unit
°C
5.0
0.0
10.0
Max Reset OAT (Cooling)
Unit
°C
15.0
10.0
30.0
Start Reset OAT (Cooling)
Unit
°C
23.0
10.0
30.0
Max Reset OAT (Heating)
Unit
°C
23.0
10.0
30.0
For heating operation
Start Reset OAT (Heating)
Unit
°C
15.0
10.0
30.0
For heating operation
Soft load control
Unit
-
Disable
Enable, Disable
Begin capacity limit
Unit
%
40
20
100
Soft load ramp
Unit
Min.
20
10
60
Current limit
Unit
-
Disable
Enable, Disable
Current limit type
Unit
-
INV
INV, CT (4-20mA)
Current limit setting
Unit
A
400
0
500
Current @20mA
Unit
A
400
0
500
Flex current limit
Unit
-
Disable
Enable, Disable
Demand limit
Unit
-
Disable
Enable, Disable
Noise reduction
Unit
-
Disable
Enable, Disable
Noise reduction start tm
Unit
-
21:00
18:00
23:59
Noise reduction end tm
Unit
-
06:00
05:00
09:59
Noise reduction Cond target
offset
Unit
°C
5
0
10
For cooling operation
Noise reduction Evap target
offset
Unit
°C
5
0
10
For heating operation
Rapid restore
Unit
-
Disable
Enable, Disable
Rapid Restore max power
failure tm
Unit
Sec.
15
15
180
Water valve ctrl
Unit
-
Disable
Enable, Disable
Chiller network control
Unit
-
Disable
Disable, Enable
Chiller network ctrl
Master / Slave
Unit
-
Slave
Master, Slave
Chiller network ctrl
Unit sequence number
Unit
-
1
4
Chiller network ctrl
Chiller network capacity limit
setting
Unit
-
Common
Common, Each
Chiller network ctrl
Light load unit stage down
Unit
%
35%
50%
Chiller network ctrl
Unit stage down timer
Unit
Min.
5
60
Chiller network ctrl
High load unit stage up
Unit
%
80%
100%
Chiller network ctrl
Unit stage up timer
Unit
Min.
5
60
Chiller network ctrl